Multi-Library Feature Engineering and Statistically Validated Classification for Power Swing Detection and Stability Assessment
2611.20364

Authors

Pallav Kumar Bera,Samita Rani Pani,Ranjeeta Patel

Abstract

Faults occurring during power swings, and the evolution of a swing into an unstable condition, cause distance-relay maloperation and cascaded outages. This paper identifies faults, faults during power swings, and power swings, and distinguishes stable from unstable swings in a 9-bus WSCC system modeled in PSCAD/EMTDC.

Three time-series feature libraries (tsfresh, TSFEL, and tsfeatures) are applied to the 3-phase relay voltages and currents, giving 3286 statistical, temporal, spectral, and fractal descriptors per event window. A two-step feature selection (Boruta all-relevant filtering followed by RFECV- and SHAP-guided minimal-optimal pruning) reduces the feature set to 18 compact, non-redundant features.

14 classifiers spanning linear, kernel/instance-based, probabilistic, neural, and tree-ensemble/boosting families are then benchmarked under repeated stratified cross-validation, with model differences assessed by a Friedman/Nemenyi omnibus-and-post-hoc test and a Nadeau--Bengio corrected paired t-test. Rotation Forest (ROF) identifies the three event types with 99.98% and SVM-RBF distinguishes stable from unstable swings with 97.97% balanced accuracy.

The results show that automated, library-driven feature extraction combined with rigorous statistical model comparison achieves near-perfect discrimination while retaining feature-level interpretability through SHAP importance.

Resources

Ray graphicRay graphicRay graphicRay graphic

Stay in the loop

Every AI paper that matters, free in your inbox daily.

Details

  • takara.ai
  • Custom AI and machine learning from the Frontier Research Team.
  • © 2026 takara.ai Ltd
  • Content is sourced from third-party publications.
Ray graphicRay graphicRay graphic