Power Setpoint Tracking for Large-Scale EV Charging: Transformer-Constrained Charging Policy Learning with Self-Tuning Constraint Prices
2611.25965

Authors

Mazaher Karimi,Xun Shen,Daniyal Sajedi-Hosseini,Yoshihiko Fujisawa,Shubham Singh

Abstract

In power setpoint tracking (PST), an operator follows a purchased charging profile without overloading shared transformers or undercharging vehicles. PST is cast as a constrained Markov decision process that minimizes tracking error subject to overload and mean user-satisfaction constraints.

Transformer-Constrained Charging Policy Learning (TC-CPL) extends soft actor-critic with proportional-integral Lagrange-multiplier updates from measured violations, a residual on the incumbent dispatcher that is warm-started from its demonstrations, and a transformer-aware encoder shared by all ports. It observes no departure times or states of charge.

Simulations (five seeds, 100 paired days) compare it with the incumbent, Round-Robin. On a 600-port, 122-substation district, raw overload falls from 3.59 to 0.0017 kWh/day (overloaded seed-days from 77% to 0.4%), and absolute tracking error falls by 27%.

Delivered energy rises by 16%, and satisfaction rises from 0.959 to 0.989. On a 42-kW transformer with household load, overload falls from 1.86 to 0.0014 kWh/day and satisfaction rises from 0.974 to 0.985, but absolute tracking error is 22% higher.

Against hand-set fixed multipliers, self-tuning is statistically indistinguishable on the district. On the single transformer, it raises satisfaction by 0.011 at similar overload, but a short sweep found a better-serving fixed pair.

The overload multipliers stay below their cap.

Resources

Ray graphicRay graphicRay graphicRay graphic

Stay in the loop

Every AI paper that matters, free in your inbox daily.

Details

  • takara.ai
  • Custom AI and machine learning from the Frontier Research Team.
  • © 2026 takara.ai Ltd
  • Content is sourced from third-party publications.
Ray graphicRay graphicRay graphic